NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since last issue.
SAFETY CONSIDERATIONS
Installing and servicing of heating and air conditioning equipment can be hazardous due to system pressures and electrical components. Only
trained personnel should install or service heating and air conditioning equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils, or cleaning and replacing filters. All other operations should
be performed by trained personnel. When working on heating and air conditioning equipment, observe precautions in literature, on tags, and on
labels attached to the unit.
Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available.
Recognize safety information. This is the safety-alert symbol
.
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the
most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or
death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage. NOTE is used
to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
This instruction covers installation of Smart Heat electric heater packages Part No. KFCEH0101H10, KFCEH0201H15, and KFCEH0301H20 into
FA4, FB4, FC4, and FX4 fan coils. Check unit rating plates for compatibility of fan coil and electric heater combinations. See Table 1 for heater
package usage.
NOTE: The Smart Heat option is for use only on heat pumps, and is not approved for any other application.
DESCRIPTION AND USAGE
The Smart Heat electric heater package options allow the addition of accessory heaters and related controls to models FA4, FB4, FC4, and FX4
fan coils with heat pump outdoor units only. See Table 1 for heater package usage.
The Smart Heat electric heater package options enhance performance of heat pump by managing the electric heat. Heating elements are staged
on individually as required to maintain dwelling set point temperature. The controller will adjust the indoor blower speed tap to reduce airflow
in the ultra comfort mode.
The controller is not a substitute for good installation and ductwork practices. All ductwork should be free of air leakage and insulated.
Performance may not be satisfactory if good practices are not followed.
NOTE: Electric heaters require a minimum airflow. See Table 2 for minimum motor speed selection before installing. There is a 1-in. minimum
clearance to combustible materials for the first 36 in. of ductwork on all fan coils with 20-kw packages, and 024, 033, and 038 size fan coils with
15-kw heater packages.
WARNING: Before beginning any installation or modification, be sure the main electrical disconnect switch(es) is in
the OFF position. Tag the disconnect with a suitable warning label. Electrical shock can cause personal injury or death.
INSTALLATION
PROCEDURE 1—INSTALL ELECTRIC HEATER ASSEMBLY
NOTE: Ensure heater coils are not deformed or damaged during heater installation.
1. Make sure power is off.
2. Remove blower access panel of fan coil unit.
Table 1—Accessory Heater Usage
ELECTRIC HEATER
PART NO.
DESCRIPTION
MODELS FA4, FB4, FC4, FX4
SIZE
KFCEH0101H10 10 kw, Non-Fused 018-036
KFCEH0201H15 15 kw, Fused 024-048
KFCEH0301H20 20 kw, Fused 030-070
Installation Instructions
KFCEH
Smart Heat
Heat Pump
Heater Packages
Form: AG-FCEH-07 Cancels: AG-FCEH-03 Printed in U.S.A. 5-00 Catalog No. 63FC-EH5
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - Installation Instructions

NOTE: Read the entire instruction manual before starting the installation.This symbol → indicates a change since last issue.SAFETY CONSIDERATIONSInsta

Page 2 - * High speed with 208v

Fig. 9—Wiring Layout of KFAIR0101ACRA0010924 VDC RELAYAUX–AUX+PCBHOT230 VAC OR 115 VAC BRANCH CKT FOR EAC24 VAC LOW VOLTAGE CKT FOR HUMIDIFIERNEUTGNDG

Page 3 - CEPL130121-01

Fig. 11—PCB SchematicA94149RW2TCW2DYOGW3Y0564897231K2 K1F1F2 LOHIK3JW2PROCESSORSEC1SEC2CAPINTERNAL FUNCTIONT1T2T39-PIN RECEPTACLETO HEATERPACKAGECLIP

Page 4

→ Fig. 12—Typical 20kw Wiring LabelA00098USE THIS LABEL ON PRODUCTS WITH NEW CONTROLS. SEEINSTRUCTION FOR DESCRIPTIONS.FMEDLO LO070060MEDLOLO033 038 0

Page 5

3. Disconnect power leads, pigtail leads (black and yellow), fan leads (yellow, red, blue, and black), primary and secondary transformer leads,and all

Page 6

1. Install control board assembly into slots on blower deck. (See Fig. 1.)2. Insert screw through mounting bracket into lip of fan coil and tighten.PR

Page 7

Table 3—Electric Heater Package DataKFCEH0101H10WATTS @ 240V: 9000230-v 208-vSINGLE CIRCUITHEATER AMPS 35.9 32.5MCA* 48.3 44.0MOP† 50 4575°C WIRE SIZE

Page 8

a. Nonprotected heaters(1.) The 10-kw heater can be wired for single supply only. Supply circuits connect to heater pigtail leads.(2.) The 10-kw heate

Page 9

b. For 15- and 20-kw fused heaters, an additional ground lug is provided on fuse mounting bracket for dual-circuit grounding. (See Fig.1.)10. Mode Sel

Page 10

C. DefrostThe Smart Heat PCB stages the correct amount of supplemental heat during defrost. If too much heat is added, the system will stay in defrost

Page 11 - INTERNAL FUNCTION

PROCEDURE 8—OPERATING AND INSTALLING CHARACTERISTICSA. PCB Component Layout, Description, and Function1. Low-voltage terminal board is used to connect

Page 12 - INSTRUCTION FOR DESCRIPTIONS

g. W2T is input from thermostat signaling for supplemental or emergency heat.h. W3 is input from outdoor thermostat. JW1 connects W3 to W2T as wired a